Life Safety (LS) (Ambulatory Health Care / Ambulatory Health Care)


ILSM - Temporary Construction Barriers
Publish | January 01, 0001
Do plastic sheets constitute acceptable temporary barriers in and around construction areas?

Unrated flammable plastic sheets, do not constitute acceptable temporary barriers. Even though flammable plastic sheets taped across an opening may form a dust seal, they are incapable of controlling fire. The only thing they can do is keep air and patriculate from moving to unwanted locations. Therefore, they are good for infection control, and on a limited basis, for resisting smoke passage caused by a fire, friction or welding/brazing in the construction zone. But these sheet types do nothing to stop the fire itself. The Joint Commission standards require that temporary construction partitions be smoke tight and built of noncombustible or limited combustible materials (sheet rock, gypsum board) that will not contribute to the development or spread of fire." Insure that evidence of "limited combustibility" can be furnished if questioned during survey or other inspection. The Joint Commission position is that plastic sheet barriers of a limited combustible type (rated material) can be used for a short term applications. In addition, if the project includes any high risk construction activities (i.e., torch cutting, welding, burning, open flame, etc.), non-combustible barriers should be erected. [LS.01.02.01]

Was this response helpful?

 
 
 
Comments (Optional - For internal use only)
Thank you for your feedback!
shareslide1